Logo FASE FASE
Strumenti elettrici di misura

Shunt DIN series      - from 1 up to 200 A


Shunt DIN series

Insulating plate only up to 25A


GENERAL FEATURES

Manufacturing:
   According to DIN 43703
Accuracy:
   cl. 0.5
Working temperature:
   from -25 up to + 40 °C
Overload:
   10 In for 5 sec. from       1 up to    250 A
     5 In for 5 sec. from   251 up to   2000 A
     5 In for 5 sec. from 2001 up to 10000 A
Complete:
   with a fixing screw to the bar
For output in mV will be supplied:
   2 screws TC M5 x 8 DIN 84-4.8
   2 washers 5,3 DIN 433-St

Voltage
drop
mV

Rated
current
A

Dimensions mm.

Connections

Weight

a1

a2

b1

c1

e

Bolts

Nuts

Kg

60

1 - 1.5 - 2.5 - 4
6 - 10 - 15 - 25

90

28

20

8

78

2x1

M5x12

-

0.2

40 - 60 - 100
150 - 200

100

33

20

8

80

2x1

M8x16

-

0.15

150

1 - 1.5 - 2.5 - 4
6 - 10 - 15 - 25

90

28

20

8

78

2x1

M5x12

-

0.20

40 - 60 - 100
150 - 200

225

33

25

8

205

2x1

M8x16

-

0.15



Precedente
Accessories for
DC instruments

Back to "Accessories for DC instruments"

Successiva
Shunt DIN series
from 250 up to 2500A


FASE - Via del Lavoro, 41 - 20030 Senago (Milano) - Italy
Tel. +39 029986557 - Fax +39 029986425